![Allen-Bradley Micro830 Manual Download Page 235](http://html.mh-extra.com/html/allen-bradley/micro830/micro830_manual_2900197235.webp)
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
221
Specifications
Appendix
A
Micro850 Controllers
The following tables provide specifications, ratings, and certifications for the
Micro850 controllers.
Micro850 24-Point Controllers
General Specifications
Attribute
2080-LC50-24AWB
2080-LC50-24QWB
2080-LC50-24QVB
2080-LC50-24QBB
Number of I/O
24 (14 inputs, 10 outputs)
Dimensions (HxWxD)
90 x 158 x 80 mm (3.54 x 6.22 x 3.15 in.)
Shipping weight, approx.
0.423 kg (0.933 lb)
Wire size
0.2…2.5 mm
2
(24…14 AWG) solid copper wire or
0.2…2.5 mm
2
(24…14 AWG) stranded copper wire
rated @ 90 °C (194 °F) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
2 – on communication ports
Wire type
Use Copper Conductors only
Terminal screw torque
0.4…0.5 Nm (3.5…4.4 lb-in.) using a 0.6 x 3.5 mm flat-blade screwdriver.
(Note: Use a handheld screwdriver to hold down the screws at the side.)
Input circuit type
120V AC
12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type
Relay
24V DC sink
(standard and high-speed)
24V DC source
(standard and high-speed)
Power consumption, max
8 W – without plug-in modules and expansion I/O modules
28 W – with plug-in modules and expansion I/O modules
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input:
120V AC 16 mA
Output:
2 A, 240V AC,
2 A, 24V DC
Input:
24V, 8.8 mA
Output:
2 A, 240V AC
2 A, 24V DC
Input:
24V, 8.8 mA
Output:
24V DC, Class 2, 1 A per point
(Surrounding air temperature 30 °C)
24V DC, Class 2, 0.3 A per point
(Surrounding air temperature 65 °C)
Isolation voltage
250V (continuous),
Reinforced Insulation Type,
Output to Aux and Network,
Inputs to Outputs.
Type tested for 60 s @
3250V DC Output to Aux and
Network, Inputs to Outputs
150V (continuous),
Reinforced Insulation Type,
Input to Aux and Network.
Type tested for 60 s @
1950V DC Input to Aux and
Network
250V (continuous),
Reinforced Insulation Type,
Output to Aux and Network,
Inputs to Outputs.
Type tested for 60 s @
3250V DC Output to Aux and
Network, Inputs to Outputs.
50V (continuous),
Reinforced Insulation Type,
Input to Aux and Network
Type tested for 60 s @ 720V
DC, Input to Aux and
Network
50V (continuous), Reinforced Insulation Type, I/O to Aux
and Network, Inputs to Outputs.
Type tested for 60 s @ 720 V DC, I/O to Aux and Network,
Inputs to Outputs.
Pilot duty rating
C300, R150
–
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
.
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...