Specifications
Appendix
A
PTO Output Duty Cycle Error
Turn On/Off time for the Micro830, Micro850, and Micro870 controllers for
the PTO output port is 0.2
µ
s and 2.5
µ
s max, respectively. Duty cycle error is:
Positive error = 2.5
µ
s * F
Negative error = -0.2
µ
s * F
The plot below shows duty cycle error vs. frequency.
To get the duty cycle error at a certain frequency, for example, the user sets
frequency to 20 kHz, and sets duty cycle to 30% in Connected Components
Workbench software, then actual duty cycle is
PTO Typical Readings
30%
+5%
-0.4%.
Error
(Per
centage
)
Frequency
0.25
0.2
0.15
0.1
0.05
0
-0.05
1000
10000
100000
Positive Error
Negative Error
PTO Typical Readings
Expected Duty Cycle
Typical Duty Cycle
(1.27 K
Ω
load)
Frequency (kHz)
%Duty Cycle
Minimum
Maximum
%Duty Cycle
5
5%
4.90%
6.25%
5.48
5
10%
9.90%
11.25%
10.5
5
20%
19.90%
21.25%
20.5
5
40%
39.90%
41.25%
40.5
5
55%
54.90%
56.25%
55.5
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...