![Allen-Bradley Micro830 Manual Download Page 179](http://html.mh-extra.com/html/allen-bradley/micro830/micro830_manual_2900197179.webp)
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
165
Use the High-Speed Counter and Programmable Limit Switch
Chapter
8
Mask for IH (HSC0.MH)
The MH (High Preset Mask) control bit is used to enable (allow) or disable (not
allow) a high preset interrupt from occurring. If this bit is clear (0), and a High
Preset Reached condition is detected by the HSC, the HSC user interrupt is not
executed.
This bit is controlled by the user program and retains its value through a power
cycle. It is up to the user program to set and clear this bit.
Mask for IL (HSC0.ML)
The ML (Low Preset Mask) control bit is used to enable (allow) or disable (not
allow) a low preset interrupt from occurring. If this bit is clear (0), and a Low
Preset Reached condition is detected by the HSC, the HSC user interrupt is not
executed.
This bit is controlled by the user program and retains its value through a power
cycle. It is up to the user program to set and clear this bit.
HSC Interrupt Status
Information
User Interrupt Enable (HSC0.Enabled)
The Enabled bit is used to indicate HSC interrupt enable or disable status.
User Interrupt Executing (HSC0.EX)
The EX (User Interrupt Executing) bit is set (1) whenever the HSC sub-system
begins processing the HSC subroutine due to any of the following conditions:
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see Count Down (HSCSTS.CountDownFlag) on page 151.
User Program Access
MH - High Preset Mask
bit
0…9
read only
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see Count Down (HSCSTS.CountDownFlag) on page 151.
User Program Access
ML - Low Preset Mask
bit
2…9
read only
Description
Data
Format
HSC
Modes
(1)
(1) For Mode descriptions, see Count Down (HSCSTS.CountDownFlag) on page 151.
User Program
Access
HSC0.Enabled
bit
0…9
read only
Description
Data
Format
HSC Modes
(1)
(1) For Mode descriptions, see Count Down (HSCSTS.CountDownFlag) on page 151.
User Program
Access
HSC0.EX
bit
0…9
read only
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...