Configuring Module Output States and Diagnostics
Configure the output states and diagnostic information for the 1756-OB16E module.
1. Click on the
Configuration
tab.
The Configuration tab appears as follows:
Note that you can configure many diagnostics and output states on the module, down to the point level.
2. Under the
Output State During
column, from the
Program Mode
pull-down menu for Point 0, choose
On
.
Choosing On will turn on output point 0 when the processor is in Program mode.
3. Repeat step 2 for output points 1, 2, and 3 as follows:
§
Output Point 1 - On
§
Output Point 2 - Hold
§
Output Point 3 - Hold
Choosing Hold for outputs 2 and 3 causes them to hold the state they were in before the processor was
changed from Run mode to Program mode.