Configure Redundancy
ControlLogix Redundancy System Overview
Redundancy requires no additional programming and is transparent to
any devices connected over an EtherNet/IP or ControlNet network. It
uses 1757-SRM modules to maintain communication between the pair
of redundant chassis.
Depending on how you organize your RSLogix 5000 project, outputs
may or may not experience a change in state (bump) during a
switchover.
•
During the switchover, outputs that are controlled by the highest
priority task will experience a bumpless switchover. For
example, outputs will not revert to a previous state.
•
Outputs in lower priority tasks may experience a change of
state.
The switchover time of a redundant system depends on the type of
failure and the network update time (NUT) of the ControlNet network.
For a NUT of 10 ms, the switchover time is approximately 80...220 ms.
Identical Pair of
ControlLogix Chassis that
Control Your Machine or
Process
At Least Two Other
ControlNet Nodes
Network 2 - ControlNet Network for I/O
Communication
Computer That Is Connected to the Network
Access Port of a Remote Node
Network 1 - EtherNet/IP or
ControlNet network for
HMI Communication
Summary of Contents for controllogix 1756-L55M12
Page 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Page 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Page 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Page 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Page 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Page 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...