Monitor Connections
If communication with a device in the I/O configuration of the
controller does not occur for 100 ms or 4 times the RPI, whichever is
less, the communication times out and the controller produces these
warnings.
•
The I/O LED on the front of the controller flashes green.
•
A
shows over the I/O configuration folder and over the
devices that have timed out.
•
A module fault code is produced, which you can access via:
–
the Module Properties dialog.
–
a GSV instruction.
Determine if Communication Has Timed Out with Any Device
If communication times out with at least one device (module) in the
I/O configuration of the controller, the I/O LED on the front of the
controller flashes green.
•
The GSV instruction gets the status of the I/O LED and stores it
in the I_O_LED tag.
•
If I_O_LED equal 2, the controller has lost communication with
at least one device.
where:
I_O_LED is a DINT tag that stores the status of the I/O LED on
the front of the controller.
!
Get System Value
CIP Object Class MODULE
CIP Object Name
Attribute Name
LedStatus
Dest
I_O_LED
GSV
Equal
Source A I_O_LED
Source B
2
EQU
Summary of Contents for controllogix 1756-L55M12
Page 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Page 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Page 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Page 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Page 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Page 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Page 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...