Kinetix 7000 Connector Data
Chapter 3
Control Power (CP) Terminal Block Connections
Kinetix 7000 drives must be wired to a 24V DC control power source through
the Control Input Power (CP) connector. The Control Power input terminal is
located on the bottom of the drive as illustrated in
.
Figure 26 - Control Power (CP) Terminal Block Detail
Table 17 - Control Power (CP) Terminal Block
Power Terminal Block (PTB) Connections
The power terminals are located behind the lower front panel of the drive. The
figures below identify the input power, motor power, DC bus, ground, and
cooling fan input terminals.
The 2099-BM09-S or 2099-BM10-S drives (frame 5), and the 2099-BM11-S or
2099-BM12-S drives (frame 6) provide connections for you to supply 120V AC
or 240V AC to power an internal cooling fan. The fan VA rating is 100 VA for
2099-BM09-S and 2099-BM10-S, and 138 VA for the 2099-BM11-S and 2099-
BM12-S drives.
The 2099-BM06-S, 2099-BM07-S, and 2099-BM08-S drives (frame 3) use the
internal power supply for fan power and thus no terminals are provided.
IMPORTANT
An external power supply provides the ability to retain control of the drive’s
logic independent of its bus power status.
Terminal
Description
Signal Name
1
Control Power 24V DC Input
CP_24VDC
2
CP_COM
CP
CP_24VDC
CP_COM
Terminal Block
(on bottom of drive)
Label
(on front of drive)