35
MASTER/SLAVE CONNECTION
BEFORE CONNECTING MASTER/SLAVE COMMUNICATION WIRES, TAKE THE FOLLOWING STEPS:
1: Test and adjust the limit switches and ERDs for each operator as stand alone machines
2: Once the machines have been adjusted, turn slave dip switch “ON” on the slave board.
Press the RESET button on the slave board or reset the power.
3: Connect the master/slave communication wires to “DATA -” and “DATA +”.
The “M/S LINK” LED should be “ON” on both machines.
4: Connect all accessories to the master operator. Accessories installed on the slave operator will not work.
.