LED DIAGNOSTICS
MODE
Blinks
once
every two seconds when there is a
problem with the motor
hall sensor
feedback. Blinks
twice every
two seconds
when a
motor overload
is
detected. Blinks
three
times every two seconds when
the gate is
jammed
.
RADIO
ON when the RADIO input is activated (closed circuit
to common).
EXIT
ON when the EXIT input is activated (closed circuit to
common).
PHANTOM LOOP
ON when the PHANTOM LOOP input is activated
(closed circuit to common).
SAFETY LOOP
ON when the SAFETY LOOP input is activated (open
circuit to common)
STOP CMD
ON when the STOP CMD input is activated (open
circuit to common)
MON_OPEN
ON when the MON-OPEN input is activated (open
circuit to open) or when a device is not installed.
MON_CLOSE
ON when the MON_CLOSE input is activated (open
circuit to common) or when a device is not installed.
TIMER
Blinks when the timer is counting down to close
automatically.
CLOSE-CMD
ON when the CLOSE-CMD input is activated (closed
circuit to common).
CLOSING
ON while the gate is in the close cycle.
OPENING
ON while the hate is in the open cycle.
CLOSE-LIMIT
ON while the limit nut is activating the close limit
switch.
OPEN-LIMIT
ON while the limit nut is activating the open limit
switch.
LOW-BATTERY
ON when the batteries are low.
ALARM
Blinks every 30 seconds (alarm will also beep) when
the batteries are low, bad, or disconnected. Turns on
for 5 minutes (alarms also goes off) when the operator
goes into shut down mode due to the gate hitting an
obstruction (ERD).
M/S LINK
ON when master/slave communication is active.
AC/PWR ON
ON when AC power is on.