
12 — Module position and circuit configuration
2902 MainStreet Technical Practices
12-3
May 2002 90-2906-01
Figure 12-1 Module positions on the Control card
12.2
Module position configuration
Primary rate module positions are not user-configurable (except for the module
name). Primary rate modules are recognized by the system during power-up and are
automatically added to the configuration database.
Interface module positions can be configured before or after the modules are
physically installed. However, a position must be configured before its circuits can
be configured or connected.
Once a module is physically installed, you can configure its position to automatically
match the module (AS_PRESENT). Once a position is configured, you can
reconfigure it as EMPTY.
After a module is installed and configured, its status should be Ok. If it is not, make
sure that the module is properly installed. If there is still a problem, check the alarm
queue (see chapter 25 in
Maintenance
).
Rather than configure each module position separately, you can configure all
positions for the modules currently installed. The positions are configured
automatically to match the installed module and are set with default values. A
position is not affected if:
•
it is correctly configured for the installed module type
•
an empty position is configured for a module type
8840
Personality
modules
(Slot 2/Slot 1)
EPROMs
Interface
module
(position 2)
Interface
module
(position 1)
3 4
1 2
LIM (P1)
Jumper blocks
(J37, J40)
Jumper blocks
(J41, J44)
LIM (P2)
Note —
Some modules have variants that are not recognized
automatically by the system. The variant is selected during module
position configuration.
Summary of Contents for MainStreet 2902
Page 1: ...2902 MainStreet Network Termination Unit Release 1 0 H T E C H N I C A L P R A C T I C E S ...
Page 40: ...3 Mounting the unit 3 8 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 50: ...4 Ground and power connections 4 10 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 68: ...6 Connecting to the network 6 4 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 90: ...7 Connecting to data devices 7 22 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 108: ...10 Node management 10 10 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 150: ...14 CPSS 14 6 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 218: ...20 Codirectional DCM 20 6 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 234: ...22 HCM rate adaption 22 10 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 246: ...23 Cross connecting circuits 23 12 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 254: ...24 Visual indicators 24 8 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 266: ...25 Alarms 25 12 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 278: ...26 System diagnostics 26 12 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 298: ...27 Loopbacks 27 20 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 332: ...Glossary GL 8 2902 MainStreet Technical Practices 90 2906 01 May 2002 ...
Page 343: ......
Page 344: ... 2002 Alcatel All rights reserved 90 2906 01 95 1820 01 00 C ...