Room Controller
Alternatively, it is able to make 2 room controller connections to LMS 14. Thus, heat demands of 2
independent primary heating circuits can be sent to LMS 14. Maximum 2 room controller connections
can be made with LMS 14.
In case of room thermostat usage, the cable terminals of the room controller device should be
connected to CL+ and CL-. The related terminal information is included in the LMS 14 connections
figure. Rapidly stating, the right terminals are X7a and X30. CL+ is the BSB (Boiler System Bus)
data connection and CL- is the BSB ground connection. These connections will also be used with
the room controller.
3.5. Flue Pipe System and Components
For boilers having a maximum capacity bigger than 50 kW’s, flue pipe outlets can not be directed
out through a side wall or window. That’s why in the below schematic picture, a flue pipe due to this
explanation is not shown.
Please don’t forget that flue pipes designed for conventional boilers can not be used in condensing
boilers, and in the contrary, the ones for condensing boilers can not be used for conventional boilers.