Translation of original operating instructions
84
AL-KO AT4F ATEX
Before commissioning, always ensure the following:
that the AT4F ATEX unit has been installed as described in these operating and assembly instructions (see chapter
"5 Assembly" on page 34).
that all the filter elements are correctly installed. Check the tight fit of all installed filters, in particular the fine dust
filters.
that the duct system and the water and drain pipe are properly connected to the unit.
that the fresh air inlet is at a sufficient distance from contamination sources (kitchen hood extraction, central dust
extraction, etc.).
that the electrical installations have been implemented completely and professionally.
that all media connections have been professionally connected and are leak-tight.
that all components are installed professionally and integrated into the unit potential, see chapter "5.2 Preparations"
on page 35
. Document this test.
that only components/components suitable for the required ATEX marking have been used.
that no impermissible changes have been made to components.
that work on/in the AT4F ATEX unit takes place during ATEX zone freedom.
6.2
Before system start
WARNING
To be carried out by the person responsible:
After carrying out the work, ensure that there are no longer any persons in the installation.
Ensure that work on/in the AT4F ATEX unit takes place during ATEX zone freedom.
Before commissioning the installation, ensure that all factory-installed protective meas-
ures are functioning correctly.
After carrying out the work, ensure that all maintenance doors, inspection covers and
housing covers are integrated into the unit potential. After each release of these equipo-
tential bonding connections, they must be restored, checked and documented.
WARNING
Risk of injuries due to run-on of fans.
Only open the inspection doors only when the fans are switched off and stationary.
Observe the delay time of the fans. Observe a waiting time of 3 minutes, until the fan im
-
pellers are stationary, before opening the inspection doors.
Never brake the impellers of the fans by hand or using an object.