Translation of original operating instructions
112
AL-KO AT4F ATEX
7.3.4.1 Maintenance
Check the damper for integration into the equipotential bonding. If necessary, the integration is to be renewed; al-
ternatively the damper is to be replaced.
Inspect the multi-leaf dampers for soiling, damage and corrosion.
Check the mechanical function of the multi-leaf dampers.
Lubricate the damper bearing and joints if necessary using appropriate lubricants.
Check the end position of the damper adjusting actuators and adjust, if necessary.
7.3.4.2 Cleaning
Clean the multi-leaf dampers at regular intervals.
7.3.5 Sound absorber
WARNING
Risk of cuts
During maintenance and cleaning of the sound attenuator splitters there is a risk of cuts.
Wear personal protective equipment (cut-proof gloves).
WARNING
Risk of explosion
Due to electrostatic charging of the sound absorber, there is a risk of explosion.
Integrate the sound attenuator splitter (with perforated plate) back into the unit potential
after each unfastening of the equipotential bonding.
ATTENTION
Observe the manufacturer's documentation.