Observe the condition of the substrate at the installation site.
Check the individual components for transport damage.
Select the installation site with regard to good accessibility for servicing and maintenance work.
Ensure that the components and the connection cables at the installation site cannot be either damaged or contam-
inated by oil or other materials.
Check that fuses, contactors and circuit boards are securely in place in the switch cabinet (optional).
Secure any loosened assemblies.
The fresh air intake must be designed in accordance with the applicable standards and should be located away from
exhaust air outlets or exhaust openings (kitchen, laundry, etc.).
If possible, the exhaust air must be discharged via a roof hood away from fresh air inlets, windows, balconies, etc.
Connect the AC unit and the unit-attached equipotential bonding to the duct system.
The integration into the equipotential bonding system of individual components in the overall system must be
checked and documented using a suitable measuring instrument.
Fig. 16 Potential equalisation mounted on the unit
ATTENTION
Components that come loose during transport can lead to malfunctions or damage.