5.8.5 Circulating coil system CCS (recuperative energy recovery)
EHA
ETA
ODA
SUP
Fig. 50 Schematic diagram of a circulating coil system
With heat exchangers in a circulating coil system, the pipe circuits themselves cannot be emptied.
For this reason, the circulating coil system is only to be operated with a frost-proof water/glycol mixture and tested for
leak-tightness after assembly.
If the system does have to be drained, the pipe circuits can be blown out with compressed air, although water still re-
mains in the heat exchanger even in this case.
ATTENTION
When using high-performance circulating coil systems, observe the manufacturer's operating
instructions.
ATTENTION
During commissioning, observe chapter "5.9.4 Filling and venting" on page 73.
Step
Action
1
Connect the heat exchanger using the counterflow principle (water flow direction opposite the air flow direction in the
unit).
2
Connect the pre flow up or down depending on the air direction.
3
Carefully vent the heat exchanger.
4
Check all of the piping for leaks.
5
Ensure that the piping and the heat exchanger are integrated into the unit potential.
Piping must be provided on-site.
Circulating pump must be dimensioned according to the technical data sheet.
Heat exchangers must be connected in the counterflow principle.
Antifreeze concentration must correspond to the specifications on the technical data sheet.
The pre flow is at the top or bottom, depending on the air direction.
We recommend the use of the antifrogen N with a mixture of 25 – 35 %.