Engineering manual
269
a)
“Comfort” button is used to select the options: current fault diagnostics- history fault
diagnostics– exit diagnostic; In current diagnostic mode,
is blinking; in history
diagnostics mode,
is light; exit diagnostic mode,
icon is off.
b)
Up to 80 current fault codes and 80 history fault codes can be browsed for IDU.
c)
Up to 10 current fault codes and 5 history fault codes can be browsed for outdoor unit.
Operation instruction
(1)
Press “COMFORT” button one time to enter current fault diagnostic mode, Press
“COMFORT” button two times to enter to history fault diagnostic mode, Press
“COMFORT” button three times to exit diagnostic mode.
(2)
Press “< button or “> button to select group or outdoor unit, ALL-1-2-…-16 is scrolled,
“ALL” is outdoor unit, 1-2-3-…16 is user address of group.
(3)
Press “OK” to confirm the selected object:
i.
If outdoor unit is selected: browse fault code by press“ ” or “ ” button, fault code will be
displayed instead of real time. Press “<” button to exit to last level.
ii.
If YY of user address of group is selected:
The min physical address of the group will displayed instead of SPT, press “ ” or “ ”
button will scroll all units’ physical address of the group, press “<” button to exit to last
level.
Press “OK” button to confirm the physical address. Press “left” button to exit to last
level.
Browse fault code by press“ ” or “ ” button, message sequence number 01-02-… is
displayed instead of real time; Time of timer area is used to display the fault code. If there
isn’t any fault code, “00” is displayed in the time of timer. Press “<” button to exit to last
level.
LWC malfunction diagnostic
(1)
Long press “COMFORT” for 5 seconds, enter diagnostics LWC itself mode,
icon is
light;
(2)
Press “ ” or “ ” button to browse LWC fault, fault code will be displayed instead of time
of timer.
(3)
Press “Comfort” for 5 seconds again, exit diagnostics LWC mode, diagnostics icon is off;
Summary of Contents for KXV Series
Page 36: ...Engineering manual 36 Heating Chart 1 1 b...
Page 69: ...Engineering manual 69 1 3 2 Exploded view Unit body exploded view Chart 1 7...
Page 70: ...Engineering manual 70 Panel exploded view Chart 1 8...
Page 75: ...Engineering manual 75 1 4 Electric board wiring diagram Chart 1 9...
Page 93: ...Engineering manual 93 2 3 2 Exploded view Unit body exploded view Chart 2 5...
Page 94: ...Engineering manual 94 Panel exploded view Chart 2 6...
Page 99: ...Engineering manual 99 2 4 Electric board wiring diagram Chart 2 7...
Page 118: ...Engineering manual 118 3 3 2 Exploded view Chart 3 6...
Page 124: ...Engineering manual 124 3 4 Electric board wiring diagram Chart 3 7...
Page 143: ...Engineering manual 143 4 3 2 Exploded view DLV007 009 012 015 exploded view Chart 4 4...
Page 144: ...Engineering manual 144 DLV018 021 024 exploded view Chart 4 5...
Page 150: ...Engineering manual 150 4 4 Electric board wiring diagram Chart 4 6...
Page 166: ...Engineering manual 166 5 3 2 Exploded view Chart 5 4...
Page 167: ...Engineering manual 167 5 4 Electric board wiring diagram Chart 5 5...
Page 182: ...Engineering manual 182 6 3 2 Exploded view PNV007 009 012 exploded view Chart 6 5...
Page 183: ...Engineering manual 183 PNV015 018 021 exploded view Chart 6 6...
Page 189: ...Engineering manual 189 6 4 Electric board wiring diagram Chart 6 7...
Page 204: ...Engineering manual 204 1 Outdoor unit Model KBTU h Brand YAV112 38 2 YAV140 47 8 Airwell...
Page 207: ...Engineering manual 207 1 2 2 Exploded view YAV112 140 Chart 1 2...
Page 210: ...Engineering manual 210 1 3 Electric board wiring diagram Chart 1 3...
Page 212: ...Engineering manual 212 Chart 1 10 Chart 1 11 Chart 1 12 Chart 1 13 Chart 1 14 Unit mm...
Page 283: ...Engineering manual 283 Chart 3 4...
Page 294: ...Engineering manual 294 4 1 Appearance RC3i 1 A Q C E F G I D H J K L M N O P B...
Page 295: ...Engineering manual 295 A B C G D F E H I J K L M N O P Q RC7i 1...
Page 372: ...Engineering manual 372...
Page 376: ...Engineering manual 376 Click the value area of axis a dialog is shown to set the range of axis...