background image

4

3 INSTALLATION GUIDELINES

1.  Prepare two circular holes in the kitchen duct   6     7   or in the kitchen hood   8   . The diameter of the holes depends 

on the diameter of the pipe you select. The diameter of the pipe should be between Ø 80 and 125 mm.

2.  Install the ozone generator.   4

The ozone generator must be installed horizontally with the suspension brackets upward and service hatch down-

ward. Use M8 threaded rods and anchor these with nuts on each side of the respective bracket. Note that the mini-

mum installation dimension for the generator is 700x500x450 mm.

AirMaid® 20000 V   Exhaust-airflow max 10000 m

3

/h  (2800 l/s)  

The generator must be easily accessible after installation. Never screw or drill through the generator. Always use the 

brackets for suspension. 

The duct connection   5   should be no more than 5m long and with a diameter of at least Ø 80 mm. The duct con-

nection must be made of stainless steel (AISI 316). Make sure that the duct does not block any inspection holes.

Note that the direction of the airflow must correspond to the arrows on the generator and the picture below. 

3.  Fasten the outlet tube   5   between the ozone generator and the kitchen duct    6     7   (or the hood   8   ). Make sure 

that the connections are properly fixed and air-tight.

4.  Connect the inlet tube   3   and the IRIS air damper   2   to the ozone generator    4   , or use a filter box with a EU3 filter.

 

When used with a central air supply, the IRIS air damper is required to achieve the proper airflow and pressure.  

For more information, see section “5 SYSTEM TEST”.

The exhaust ducts must be swept clean of grease and soot at the time of installation. This is required to achieve the 

desired result of the ozone cleaning.

1

1

2

2

3

3

4

4

5

5

6

6

A

A

B

B

C

C

D

D

Designed by

Checked by

Approved by - date

Material

Edition

Sheet

/

Date

 

AM 20000V monterings

anv manual 1 (12-12-04)

Mikael

 

 

 

2012-12-04

 

 

Scale

 

Project

 

302

616

574

25

2

404

125

300

To hood or exhaust duct

2 x 30+/-10l/s (Target: 2 x 35 l/s)

Minimum 1m

Air Damper

To hood or exhaust duct

AirMaid® Ozone Unit

AirMaid® Ozone Unit

Clean Air 2 x 30 +/- 10 l/s (Target: 2 x 35 l/s)

Summary of Contents for AirMaid V

Page 1: ...Installation and service guide for AirMaid V ozone cleaning system 20 000 V AirMaid ozone cleaning system Innovative Air Treatment ...

Page 2: ...defective part and includes labor charges according the recommended hours by Interzon and maximum kilometer charges of 300 km round trip The warranty for spare parts covers only the repair or replacement of the defective part and does not include any labor charges for the removal and installation of any parts travel or other expenses incidental to the repair or replacement of a part Any claim must...

Page 3: ... order to reduce the frequency of filter changes the supply air should originate from a place containing the least possible impurities The tempera ture of supply air should not exceed 40 C AirMaid is very effective in reducing odors provided that the reaction time between the ozone and the exhaust air in the kitchen duct is at least 2 seconds This reaction time is important and must be taken into ...

Page 4: ...ct does not block any inspection holes Note that the direction of the airflow must correspond to the arrows on the generator and the picture below 3 Fasten the outlet tube 5 between the ozone generator and the kitchen duct 6 7 or the hood 8 Make sure that the connections are properly fixed and air tight 4 Connect the inlet tube 3 and the IRIS air damper 2 to the ozone generator 4 or use a filter b...

Page 5: ... customers NOTE Upon delivery the generator and alarm panel within the shipping carton are calibrated together and have matching serial numbers Make sure that generators are always connected to their own alarm panel If you desire to connect AirMaid to an external monitoring or alarm system you can accomplish this by connecting it to the external alarm terminal block within the AirMaid alarm panel ...

Page 6: ...f the generator according to the instructions found in this manual Call Service The RED lamp is flashing An error has lasted for more than 72 hours Contact the service company to remedy the error Press or to step through menu options or reposition the cursor Press or to change the value Press to select the current option Press for 5 seconds to save the displayed value To ENTER the settings menu Pr...

Page 7: ...ode will automat ically exit after one hour Set alarm delay By default the delay is set to 5 minutes in order to prevent an alarm in case of a temporary disruption Set inspect freq Service and maintenance interval in months Perform Recalibration This menu option must be used after the generator has been repaired and electronic components have been replaced Do not recalibrate at any other time EXIT...

Page 8: ... Ensure that the electrical wiring is correctly installed 3 Ensure that the exhaust fan is running 4 Ensure that the grease filters are properly installed in the hoods in the kitchen 5 Ensure that the main power switches are ON red light must glow at the ozone generators 6 Ensure that the interlock is working properly 7 Ensure that there is no leak in the tubing after the ozone generator 8 If the ...

Page 9: ...t the glass electrodes of the ozone cells are not damaged or cracked A proper ozone cell should be clean and free from any mechanical damage according to the picture to the right above 4 Clean the glass electrodes carefully with a soft towel together with some cleaning spirit Never use any sharp tools or abrasive materials for cleaning the glass electrodes 5 Close the service hatch and switch ON t...

Page 10: ...e end user wishes to discard this product it must be sent to separate collection facilities for recycling Facts about Ozone Ozone is a colorless gas with a pungent smell that can be detected by any person at a concentration of 0 02ppm 0 4mg m3 The smell of ozone is similar to chlorine like in a swimming baths Local protection legislations must be followed when using ozone In Sweden the Swedish Wor...

Page 11: ...ail Contact name Telephone E mail Product Serial No Date of installation mm dd yy Generator Airflow l s Generator Pressure Pa 8 AIRMAID Product Registration INSTALLATION SERVICE COMPANY Place of Installation PRODUCT IDENTIFICATION FROM SYSTEM TEST Interzon AB Phono 46 8 544 444 30 Propellervägen 4A Fax 46 8 544 444 39 SE 183 62 Täby Stockholm Email info interzon com Sweden Internet www interzon co...

Page 12: ...SE 183 62 Täby Stockholm Email info interzon com Sweden Internet www interzon com Reproduction modification or translation without a prior written consent is forbidden with the exception of what is permitted by the Act on Copyright Original instructions 2012 Copyright Interzon AB Edition 2 05 2013 ...

Reviews: