9
The ozone cells inside the ozone generator must be checked and if necessary cleaned at least once a year according to
the instructions be
low. If a separate air filter is used for the inlet air, make sure that this filter is changed at least one time
per year. After a new installation it is anyhow recommended to make an inspection already after three months. Always use
protective gloves and protective goggles.
1. Switch OFF the main power to the ozone generator.
2. Open the service hatch on the bottom of the ozone generator.
3. Make sure that the glass electrodes of the ozone cells are not damaged or cracked.
A proper ozone cell should be clean and free from any mechanical damage according to the picture to the right above.
4. Clean the glass electrodes carefully with a soft towel together with some cleaning spirit. Never use any sharp tools
or abrasive materials for cleaning the glass electrodes.
5. Close the service hatch and switch ON the main power on the ozone generator. Make sure that the generator starts
by checking the alarm panel. If everything works the green lamp will glow. If the red lamp flashes then see –
“TROUBLESHOOTING”.
6 SERVICE AND MAINTENANCE
If any work needs to be performed
in the kitchen extraction ducts, the
power to the ozone generator must
be disconnected.