8
Measure the airflow through the ozone generator and note the value here __________
Measure the pressure inside the ozone generator and note the value here __________
The values above must be entered in the supplied product registration form.
The specified airflow must be 30±10 l/s and the specified pressure must be less than -20 Pa (max -10 kPa). Usually the
airflow is measured over the damper while the pressure can be measured from the pressure checkpoint on the long side
of the ozone generator.
1. Ensure that the correct airflow and pressure is maintained according to the specification.
2. Ensure that the electrical wiring is correctly installed.
3. Ensure that the exhaust fan is running.
4. Ensure that the grease filters are properly installed in the hoods in the kitchen.
5. Ensure that the main power switches are ON (red light must glow) at the ozone generators.
6. Ensure that the interlock is working properly.
7. Ensure that there is no leak in the tubing after the ozone generator.
8. If the ozone generator is installed with a filter box, make sure that the filter is clean.
9. If the system still does not start call the distributor or the manufacturer.
5 SYSTEM TEST
AIRFLOW AND PRESSURE
TROUBLESHOOTING
To hood or exhaust duct
2 x 30+/-10l/s (Target: 2 x 35 l/s)
Minimum 1m
Air Damper
To hood or exhaust duct
AirMaid® Ozone Unit
AirMaid® Ozone Unit
Clean Air 2 x 30 +/- 10 l/s (Target: 2 x 35 l/s)