2.3 – INPUTS/OUTPUTS
Analog Inputs
. Dual inputs are field configurable via
jumper for 0-5VDC, 0-10VDC, or 4-20mADC. One is
reserved for temperature input; the other for use with
special function.
Analog Outputs
. Three standard and one selectable
outputs are individually configurable via jumper for 0-
5VDC, 0-10VDC or 4-20mADC.
Digital Inputs
. Dry contacts for AUTO-purge external
start command and purge interrupt.
Digital Outputs
. Dry contacts for optional alarm or AUTO-
purge activation and acknowledgment. Contacts rated for:
Maximum 3 amps @ 24 to 120VAC
Maximum 3 amps @ 24VDC
Maximum 0.5 amps @ 48VDC
Temperature Compensation Selection
. Push-button
selection of linearized or non-linear input. Choice of thermo-
couple or 100 ohm platinum RTD temperature sensor type.
Type E
-50 to 1750ºF
-50 to 950ºC
Type T
-50 to 750ºF
-50 to 400ºC
Type J
-50 to 2000ºF
-50 to 1090ºC
Type K
-50 to 2000ºF
-50 to 1090ºC
RTD
-50 to 1500ºF
-50 to 815ºC
Pressure Compensation
. Absolute pressure
(atmospheric or duct static), up to 60 IN Hg.
Network Communication
. Optional ModBus TCP/IP
over Ethernet.
2.4 – POWER
Power Supply
. 24VDC or 24VAC. Optional 120VAC via
external UL listed transformer.
Power Consumption
.
Circuit Protection
. Power input is isolated, fused, and
reverse polarity protected.
2.1 – TRANSMITTER
Ranges
. Natural Spans
.
0 to 25.00 IN w.c.
0 to 10.00 IN w.c.
0 to 5.00 IN w.c.
0 to 2.00 IN w.c.
0 to 1.00 IN w.c.
Span Rangeability.
The calibrated span can be down
ranged to 40% of the Natural Span.
Accuracy
. ±0.1% of Natural Span, including non-
linearity, hysteresis, deadband, and non-repeatability.
Stability
. ±0.5% of Natural Span for six months.
Transducer Response Time
. 0.5 second to reach
98% of a step change.
Temperature Effect
.
Zero. None; corrected by AUTO-zero.
Span. 0.015% of Full Span/ºF.
Mounting Position Effect
. None; corrected by AUTO-
zero.
Span and Zero Adjustment
. Digital, via internally
located push-buttons.
Automatic Zeroing
.
Accuracy. Within 0.1% of calibrated span.
Frequency.Every 1 to 24 hours selectable on 1 hour
intervals.
Low Pass Filtration
. Response time to reach 98% of
a step change is adjustable from 2.0 to 256.0 seconds.
Overpressure and Static Pressure Limit
. 25 psig.
Temperature Limits
.
–20 to 180ºF Storage.
+40 to 140ºF Operating.
Humidity Limits
. 0-95% RH, non-condensing.
2.2 – INDICATION
Displays
. Graphical backlit LCD provides up to five
lines of data display.
SECTION 2 – PERFORMANCE SPECIFICATIONS
2 – PERFORMANCE SPECIFICATIONS
0 to 0.50 IN w.c.
0 to 0.25 IN w.c.
0 to 0.10 IN w.c.
0 to 0.05 IN w.c.
24VAC
24VDC
120VAC
14.4VA
9.6W
19.2VA
14VA
9.0W
18.67VA
85VA
37W
106VA
73VA
37W
92VA
Standard
w/AUTO-purge