
CAMM
Air Monitor Corporation
116-044-91.P65 (8/31/10)
CAMM - IO&M Manual
5.12 – SPECIAL FUNCTION CONFIGURATION
Operator can turn Special Function ON or OFF, select type of function (See Section 3.6 – Features, for description of
the different special functions), and set the following values:
External Input Maximum
: This value represents the maximum value of the external input. This value is used if
External Special Function Input is selected as a display parameter.
Percent Deviation Setpoint
: (Note: Available only if Percent Deviation is selected as Function Type.) The percent
difference between the transmitter signal and an external input that will cause an alarm condition when exceeded.
Alarm Deadband
: (Note: Available only if Percent Deviation is selected as Function Type.) A percentage below the
percent deviation setpoint which the deviation must reach to reset an activated alarm.
Alarm Delay
: (Note: Available only if Percent Deviation is selected as Function Type.) Time between an alarm
condition existing and alarm activation. Adjustable between 0.0 and 10.0 minutes in 0.1 minute increments.
SECTION 5 – OPERATION
33
SECTION 5 – OPERATION
Default selection shown.
Available selections:
- AUTO-purge Configuration
Special Function Config.
- K-Factor Configuration
- Special Func Off / On Selection
- Function Type Selection
- Extrnl Input Maximum Selecton
- % Deviation Setpoint Selection
1
- % Dev Alarm Dead Band Selection
1
- % Dev Alarm Delay Selection
1
- Return to Main Menu
Special Func. Off / On
OFF
Function Type
% Deviation
% Deviation Setpoint
10.00%
%Dev Alarm Dead Band
0.00%
% Dev Alarm Delay
5.0 Min.
1 Avail. only if % Deviation is selected
as Function Type
OFF or ON
% Deviation 2
Summed Flow
2
Averaged Flow
2
Delta, Int. - Ext. 2
Delta, Ext. - Int. 2
Low Select
High Select
0.00 to 100.00%
in 0.01 increments
0.00 to 100.00%
in 0.01 increments
0.0 to 10.0 Min.
in 0.1 increments
Special Function Config.
Return to
MAIN MENU
Extrnl Input Maximum
FLOW 10,000 CFM
Uses Process Units
& Format Selected
in Process Config.
2
Available only if Process
Type is Flow.
Operator Setup Main Menu
Summary of Contents for CAMM
Page 2: ......