CAMM - IO&M Manual
7
4.5 – POWER/SIGNAL CONNECTIONS
All power and signal wiring is done at the terminal strip at the left side of the CAMM. Figure 4.3 below represents the
terminal strip and the connections for power input and the various inputs/outputs available.
Figure 4.3
CAUTION
When connecting or disconnecting any wiring to the CAMM, the
unit's power switch (see Figure 4.1) must be in the OFF position.
WIRING
.
It is recommended that any power wiring be 14 awg to 18 awg, and any signal wiring should be 14 awg to 22 awg. 14
awg is the maximum wire gauge that the terminal strip on the CAMM can accommodate.
No more than two wires should be connected to any one terminal. 18 awg is the maximum gauge wire that can be
doubled up in one terminal on the CAMM.
To facilitate wiring and any future removal of the CAMM, each terminal strip is removable from the unit. Remove
terminal strip marked 1-16 first by pulling sideways, away from the unit. A flat blade screwdriver can also be used to
gently pry strip free. Once the strip is removed, the second strip marked 17-32 can be similarly removed.
If the unit was furnished with optional conduit connection box, loosen screw, and remove cover to gain access to the
terminal strip.