SECTION 6 – CALIBRATION
6.3 – TRANSMITTER INPUT CALIBRATION (con't)
6.3.2
(con't)
Note: If span input is less than 80% or greater than 120% of Absolute Pressure maximum input (see
Factory Set-Up Information Sheet), display will indicate:
Bad Input Span
-- Push ESCAPE --
If this occurs, check input pressure (as read on gauge), and readjust as necessary. Press
ESC
and
repeat Steps 7 through 10.
11. Press
ESC
.
12. Remove test equipment.
52