![Air Monitor CAMM Installation, Operation And Maintenance Manual Download Page 35](http://html.mh-extra.com/html/air-monitor/camm/camm_installation-operation-and-maintenance-manual_2875323035.webp)
CAMM
Air Monitor Corporation
116-044-91.P65 (8/31/10)
CAMM - IO&M Manual
SECTION 5 – OPERATION
30
5.9 – LOW PASS FILTER SELECTION
User can select level of filtering applied to the transducer output*. Levels are 0 to 8, with 0 representing no
filtering, 1 representing minimal filtering (0.5 sec time constant), and 8 representing maximum filtering (64 sec time
constant).
*This filtering affects all subsequent outputs, displays, special function, alarms, etc., that utilize the transducer output.
1. While in Main Menu, use
UP
or
DN
to scroll to:
Low Pass Filter
Selection
2. Press
ENT
and display indicates current setting of Low Pass Filter; 0 (none) to 8 (Maximum).
3. Use
UP
or
DN
to change setting. Once desired setting is displayed, press
ENT
and new setting will be stored in
memory and display will return to Main Menu.
Note: If user desires not to change the setting and return to Main Menu, press
ESC
. Unit will remain
programmed as it was originally.
- Trans. Scaling & Config.
Low Pass Filter Selection
- Auto-Zero Configuration
Low Pass Filter
1 (Minimum)
0 (none) to
8 (Maximum)
Default selection shown.
Available selections:
Operator Setup Main Menu
Summary of Contents for CAMM
Page 2: ......