CAMM
Air Monitor Corporation
116-044-91.P65 (8/31/10)
CAMM - IO&M Manual
SECTION 5 – OPERATION
5.8 – TRANSMITTER SCALING & CONFIGURATION (con't)
19
- Process Configuration
- Temperature Configuration
1
- Absolute Pressure Configuration
2
- Calc. for Max Diff Pres or Flow
3
- Return to MAIN MENU
ON or OFF
Density Comp
Off/On Selection
Density Comp Off/On
ON
Process Configuration
MASS
or
VOLUMETRIC
Density Comp Type
Selection
4
Density Comp Type
MASSFLOW
See UNITS list for
availableselections
Process Units
Selection
Process Units
FLOW SCFM
See FORMAT list for
available selections
Process Format
Selection
Process Format
FLOW
XX,XXX
SCFM
Depends on
Process
Type and Format
Process Minimum
Selection
Process Minimum
FLOW 0 SCFM
Depends on
Process
Type and Format
Process Maximum
Selection
Process Maximum
FLOW 10,000 SCFM
°F, °C, °R or °K
Temperature Units
Selection
Temperature Units
°F
in.Hg, psia, kPa,
mbars or mm WC
BarometricPresUnits
Selection
Barometric PresUnits
in.Hg
0% to 100.00%
in 0.01 increments
Output Lockdown
Selection
6
Output Lockdown
10.00% FS Output
3
Available only if Square Root is ON in
Process Configuration.
4 Available only if Density
Compensation is ON.
Trans. Scaling & Configuration
Default selection shown
.
Available selections:
TEMP. & PRES.
TEMP. Only
PRESSURE Only
Temperature/Pressure
Selection
Temperature/Pressure
TEMP. and PRESS.
Square Root Off / On
ON
Square Root Off/On
Selection
5
ON or OFF
Process Type
Selection
6
Process Type
Transmitter Flow
Transmitter Flow
or
TransmitterVelocity
EXIT
1
Not
available if PRESSURE Only is
selected in Process Configuration.
2 Not
available only if TEMPERATURE
Only is selected in Process Config.
5 Available only if Density
Compensation is OFF.
6 Not available if Square
Root is OFF. If Square Root
is OFF, Process Type is
Differential Pressure (D.P.).
Sq. Feet; Sq. Inches
Sq. Meters; or
Sq. Centimeters
Duct Area Units
Selection
7
Duct Area Units
Square Feet
7
0.00
to
325.0 Sq. Ft.
Duct Area
Selection
7
Duct Area
10.00 Sq Ft
Duct Area Range
0.00 - 325.00 Sq Ft
0.0000 - 3.2500
0.000 - 32.500
0.00 - 325.00
0.0 - 3250.0
Duct Area Range
Selection
7
Exits to Trans.
Scaling &
Configuration Menu
7 Available only if Process
Type is Transmitter Flow.
Available units depends on
Process Type selected.
Operator Setup Main Menu
- Operator Password Selection
Trans. Scaling & Config.
- Low Pass Filter Selection