USE OM
– JANUARY 2017
22
APPENDIX B: CONDENSER CURVE INFORMATION
Purpose
This appendix shall:
Characterize the refrigeration effect (capacity) and power of the Highest Sales Volume Tested
Combination (HSVTC) Outdoor Unit independent of the Indoor Unit and its associated power;
Provide a standardized, general equation form to characterize Outdoor Unit performance and
power; and
Provide a method of identifying the equation coefficients required for the capacity and power
equations.
Scope
The methods outlined herein are applicable to:
HSVTC Outdoor Units that are used for cooling only applications;
HSVTC heat pump Outdoor Units, cooling only performance and power; and
AHRI/DOE A, B, C, D, F, and H test conditions as defined in AHRI Standard 210/240.
Definitions
Condensing Unit
– Consists of the Outdoor Unit and all interconnecting lines, liquid and suction,
used to connect the outdoor refrigeration system to the Indoor Unit.
Condenser performance is characterized by the general linear equation:
Gross Capacity or Power = m · (Evaporator Saturation Temperature) + b
Where;
m = slope
b = intercept
Condenser power
– power, watts, associated with the Outdoor Unit only; no indoor power is to be
included.
Condenser capacity
– total capacity, Btu/h, with no indoor power.
Evaporator Saturation Temperature
– the refrigerant saturation temperature based on the outlet
refrigerant pressure of the evaporator.
HSVTC
– Highest sales volume tested combination.
Liquid temperature
– the mean of the actual liquid temperature, °F, measured at the inlet to the
evaporator flow control during HSVTC tests.
Requirements
The following information is required for AHRI submittal of each HSVTC Outdoor Unit and heat pump:
Table B1: AHRI Submittal Requirements for High or Single Stage
Item
Definition
m1
Slope of capacity equation, A-test
m2
Slope of power equation, A-test
m3
Slope of capacity equation, B-test
m4
Slope of power equation, B-test
b1
Intercept of capacity equation, A-test
b2
Intercept of power equation, A-test
b3
Intercept of capacity equation, B-test
b4
Intercept of power equation, B-test
TL A
Liquid temperature entering flow control, A-test