Installation and Configuration
Soloist Hardware Manual
2-10
www.aerotech.com
2.6
Emergency Stop Sense Input (TB101)
If you purchased the -AUXPWR option, the opto-isolated input (PS2806-1 device)
activates by an external fail-safe emergency stop circuit. It is not intended to be an
emergency stop circuit in itself. It is scaled for a 24 volt input voltage, or a 5 volt input by
changing JP6 as shown in the following table. Using a higher input voltage requires
adding an external series resistor to limit the current.
If the ESTOP bit is enabled in the FaultMaskGlobal axis parameter (see the Soloist Help),
the ESTOP input must be driven to prevent the ESTOP fault condition.
For typical ESTOP wiring, see the following schematic and interface drawing.
Table 2-4
ESTOP Input Voltage Jumper
Jumper #
Setting
Description
1-2*
24 Volt DC Input
JP6
2-3
5 Volt DC Input
* Factory default setting
Figure 2-6
ESTOP Sense Input (TB101)
Connecting the E-Stop input to a relay or other noise producing device/circuit,
requires one or more noise suppression devices, such as those in Table 2-5, or other
appropriate devices.
Table 2-5.
Electrical Noise Suppression Devices
Noise Suppression Device
Aerotech P.N.
Third party P.N.
RC (.1uf / 200 ohm) Network
EIC240
Electrocube RG1782-8
Varistor
EID160
Littlefuse V250LA40A
WARNING
Summary of Contents for SOLOIST
Page 20: ...Introduction Soloist Hardware Manual 1 10 www aerotech com...
Page 50: ...Technical Details Soloist Hardware Manual 3 6 www aerotech com Figure 3 3 User Outputs J104...
Page 78: ...Soloist Options Soloist Hardware Manual 4 14 www aerotech com...
Page 88: ...Accessories Soloist Hardware Manual 5 10 www aerotech com...
Page 96: ...Troubleshooting Soloist Hardware Manual 6 8 www aerotech com...
Page 114: ...Index Soloist Hardware Manual iv www aerotech com...
Page 116: ......