Installation and Configuration
Soloist MP
2.4.1. Typical ESTOP Interface
The user can connect an external emergency stop relay circuit to the Soloist MP’s motor power supply input.
This will remove power to the motor while maintaining control power, as shown in the
.
The external relay must be sized based on the number of the Soloist MPs connected and the peak current
rating of each drive.
Figure 2-28:
Typical Emergency Stop Circuit
Table 2-27:
Typical ESTOP Relay Ratings
Axes
DC1
Aerotech P/N
Third Party P/N
Up to 5
32
ECW01024
Sprecher & Schuh CA7-16C-M40-24D
N O T E :
Multiple contacts are used in series to achieve desired DC contact rating.
www.aerotech.com
Chapter 2
57
Summary of Contents for Soloist MP 10
Page 1: ...Revision 4 10 00 Soloist MP Hardware Manual...
Page 6: ...Soloist MP Table of Contents 6 www aerotech com This page intentionally left blank...
Page 14: ...Soloist MP Quick Installation Guide 14 www aerotech com This page intentionally left blank...
Page 77: ...IO Expansion Board Soloist MP Figure 3 13 PSO Interface www aerotech com Chapter 3 77...
Page 78: ...Soloist MP IO Expansion Board 78 Chapter 3 www aerotech com This page intentionally left blank...
Page 81: ...Accessories Soloist MP Figure 4 2 Two Axis Joystick Interface www aerotech com Chapter 4 81...
Page 86: ...86 Chapter 5 www aerotech com Soloist MP Maintenance This page intentionally left blank...
Page 90: ...Soloist MP Revision History 90 Appendix B www aerotech com This page intentionally left blank...
Page 94: ...Soloist MP Index 94 www aerotech com This page intentionally left blank...