44
www.aerex.de
Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2021]
9.13 Type 12: Alarm indicating that the comfort T° is too low relative to setpoint T°
• Conditions:
• Only with post-heating option.
• Causes:
• The comfort T° setpoint cannot be reached (actual T° lower than setpoint during 15 minutes, or
30 minutes if comfort on T2 instead of T5, while post heating is at maximum.)
• Effects:
Displayed on Touchpanel
Text displayed
LED ALARM
LED Pa
S.50
Post-heating - T° of the supply air too low
RED
/
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
/
/
ON
/
/
Auto reset: yes