39
www.aerex.de
Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2021]
9.4 Type 4: Alarm indicating the system cannot fulfil the setpoint
• Conditions:
• Causes:
• The setpoint cannot be fulfilled because the upper or lower limit of the fan’s working zone has
been reached
• Effects:
Displayed on Touchpanel
Text displayed
LED
ALARM
LED
Pa
S.11 “Constant Pressure” fan 1 – Measured pressure too high – Minimum air flow reached
RED
/
S.12 “Constant Pressure” fan 1 – Measured pressure too low – Maximum air flow reached
S.13 “Constant Pressure” fan 3 – Measured pressure too high – Minimum air flow reached
S.14 “Constant Pressure” fan 3 – Measured pressure too low – Maximum air flow reached
S.20 „“Demand control” fan 1 – Air flow too low – Reduce the pressure on this fan
S.21 “Demand control” fan 1 – Air flow too high – Minimum limit of the motor reached
S.22 “Demand control” fan 2 – Air flow too low – Reduce the pressure on this fan
S.23 “Demand control” fan 2 – Air flow too high – Minimum limit of the motor reached
S.24 “Demand control” fan 3 – Air flow too low – Reduce the pressure on this fan
S.25 “Demand control” fan 2 – Air flow too high – Minimum limit of the motor reached
S.34 “Constant Air Flow” fan 3 – Air flow too low – Reduce the pressure on this fan
S.35 “Constant Air Flow” fan 3 – Air flow too high – Minimum limit of the motor reached
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
/
/
ON
/
/
Auto reset: yes
* unless the status has been changed in advanced setup
9.5 Type 5: Alarm indicating a data failure in the control circuit
• Conditions:
• Causes:
• Crucial data from the circuit board has been lost
• Effects:
Displayed on Touchpanel
Text displayed
LED ALARM
LED Pa
D.10
Programme Error
RED
/
D.20
Data Error
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
Alarm status
/
ON
/
Stopped
Auto reset: no
• Solutions:
• Try a TOTAL RESET of the data using the advanced setup. If still not resolved, order a new circuit