37
www.aerex.de
Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2021]
9.2 Type 2: Alarm on the pressure variation
• Conditions:
• Mode airflow control or demand control. Unit must have forward fans or backward fans with
DDM kit.
• External pressostat connected on IN2 input
• Causes:
• Pressure alarm setup in airflow control or demand control mode
• External pressostat connected on IN2 input has triggered
• Effects:
*
unless the status has been changed in advanced setup
Displayed on Touchpanel
Text displayed
LED ALARM
LED Pa
P.10
Pressure alarm - Supply air
/
RED
P.20
Pressure alarm - Extract air
S.40
Pressure alarm from Pressure Switch*
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
/
Closed
ON
/
Run*
Auto reset: yes