9.21 Type 20: Alarm Indicating that the defrost process is active
• Conditions:
• Unit with counter flow heat exchanger.
• Causes:
• The ice forming inside of the plate heat exchanger is genrating a pressure drop that is to high for
the current airflow. This detection requires a Modbus pressure sensor placed on the heat ex-
changer and that the modulation of the fans speed is based on the airflow and not on torque.
• When the previous detection is not available, the supply T° is checked and if it falls below 11°C,
it is considered that is due to the ice that reduces the heat exchanger efficiency.
• Effects:
Displayed on Touchpanel
Text displayed
LED ALARM
LED Pa
B.20
Incorrect position of the modulating bypass.
RED
/
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
Alarm Status
/
ON
/
Stopped
Manual reset mandatory.