Temperature
The temperature control can be configured as a supply air
control or an extract air control. By default, this function is
configured as a supply air temperature control. Changes
to this configuration are done in the advanced setup;
see Section 7.1.4
Setting
Settings range
Factory setting
T° Heating
0...45 °C
20,0 °C
T° Cooling
0...99 °C
24,0 °C
T° Freecooling
0...99 °C
15,0 °C
Fire Alarm
An external fire detection system is used to control the air
handling unit in case of emergency. The fire alarm function
is activated by means of digital input IN3.
Setting
Settings range
Factory setting
Input
Normally open
Normally closed
Normally
closed
Supply airflow
0...max
Extract airflow
0...max
Periodic maintenance
Built-in timer for maintenance warning; if the maintenance
interval is exceeded, a maintenance reminder will be dis-
played.
Setting
Settings range
Factory setting
3 monthly warning
Yes
No
No
12 monthly warning Yes
No
Yes
Commissioning completed
When the commissioning has been successfull and this is
confirmed in this menu, the commissionig menu will not
be activated automatically anymore.
Setting
Settings range
Factory setting
Confirmation of
successfull
commissioning
Yes
No
No