Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2021]
External coils
Configuration of the coils
This menu will allow for the configuration of any com-
bination of external heating and or cooling coil(s).
Setting
Settings range
Factory
setting
Type
None
Hot water
Cold water
Hot & Cold water
Reversible water
Electric PWM
Electric PWM + Cold water
Water preheating
Water prepostheating
Water prereversible
Electric 0...10V
Electric 0...10V + Cold water
None
Water post heating
The external post heating coil is delivered seperately
from the air handling unit and will not be pre config-
ured in factory. Both the coil and the 3-way valve will
have to be installed and wired on site. The capacity
of the coil will be controlled proportionally in order to
keep a temperature as defined by the selected oper-
ating mode. The reaction speed can be set. A higher
Setting will result in a faster reaction speed; a lower
Setting will result in a slower reaction speed.
Setting
Settings range
Factory setting
Control mode
Exhaust
Supply
Supply
Setpoint
0...99,9 °C
21,0 °C
Reaction Speed 1...10
5
Water cooling coil
The external post cooling coil is delivered seperately
from the air handling unit and will not be pre config-
ured in factory. Both the coil and the 3-way valve will
have to be installed and wired on site. The capacity
of the coil will be controlled proportionally in order to
keep a temperature as defined by the selected operat-
ing mode.
Setting
Settings range
Factory setting
Control mode
Exhaust
Supply
Supply
Setpoint
0...99 °C
17,0 °C
Reaction Speed 1...10
5
Electrical postheating coil
The external post heating coil is delivered seperately
from the air handling unit and will not be pre config-
ured in factory. The coil will have to be installed and
wired on site. The capacity of the coil will be con-
trolled proportionally in order to keep a temperature as
defined by the selected operating mode.
Setting
Settings range
Factory setting
Control mode
Exhaust
Supply
Supply
Setpoint
0...+99 °C
21,0 °C
PID - Proportion-
al Band
0...100
5
PID - Integral
0...100
30
PID - Derivate
0...100
11
Combi coil
The external change over coil is delivered seperately
from the air handling unit and will not be pre config-
ured in factory. The coil will have to be installed and
wired on site. The capacity of the coil will be con-
trolled proportionally in order to keep a temperature as
defined by the selected operating mode.
Setting
Settings range
Factory setting
Activate change
over
No
Yes
No
Neutral band
High
0...+50 °C
4K
Neutral band
Low
0...+50 °C
2K