Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0078_0M
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
45
of
216
GF-128
Phone: 800-526-0288
09/11/2015
Table 3-4. Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F (54.4°C)
2
Unit Type
Innovation WH
Innovation WH
3
Unit Size
600, 800, 1060, 1350 MBH
(175.8, 234.5, 310.7, 395.6 kW)
600, 800, 1060 or
1350 MBH
4
Fuel Type
Natural Gas, Propane
Natural Gas
5
Water Heater Mode
Constant Setpoint,
Remote Setpoint,
Constant Setpoint
6
Remote Signal
(If Mode = Remote Setpoint,
Direct Drive or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS),
Network
4 – 20 mA,
1-5V
7
Outdoor Sensor
Enabled or Disabled
Disabled
8
System Start Tmp
(If Outdoor Sensor =Enabled)
30°F (-1.1°C)
100°F (37.8°C)
60°F (15.5°C)
9
Setpt Lo Limit
40°F (4.4°C)
Setpt Hi Limit
60°F (15.5°C)
10 Setpt Hi Limit
Setpt Lo Limit
190°F (87.8°C)
150°F (65.6°C)
11 Temp Hi Limit
40°F (4.4°C)
200°F (93.3°C)
160°F (71.1°C)
12 Max Valve Position
40%
100%
100%
13 Pump Delay Timer
0 min.
30 min.
0 min.
14 Aux Start On Dly
0 sec.
120 sec.
0 sec.
15 Failsafe Mode
Shutdown or Constant Setpt
Shutdown
16 * Analog Output
Off, Setpoint, Outlet Temp, Valve Pos
4-20mA, valve Pos 0-10v
Valve Pos 0-10v
17
Low Fire Timer
2 sec.
600 sec.
2 sec.
18
Setpt Limiting
Enabled or Disabled
Disabled
19
Setpt Limit Band
0°F (0°C)
10°F (5.5°C)
0
20
Network Timeout
5 Sec
999 Sec
30 Sec
21
Shutoff Dly Temp
0
25
8
22
Demand Offset
0
25
5
23
Deadband High
0
25
0
24
Deadband Low
0
25
0