Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 8 – WATER HEATER MANAGEMENT
OMM-0078_0M
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
121
of
216
GF-128
Phone: 800-526-0288
09/11/2015
WHM MENU
See section 8-6 for a range of choices and the default values.
ITEM
MENU LEVEL &
OPTION
DESCRIPTION
13
WHM Min Addr
Set the minimum address of the heaters to be controlled by the
master. The
WHM Min Addr
and
WHM Max Addr
must differ by no
more than 7.
14
WHM Max Addr
Set the maximum address of the heaters to be controlled by the
master. The
WHM Min Addr
and
WHM Max Addr
must differ by no
more than 7.
15
SSD Address
The Modbus Address of the SSD Device (Protonode). Set this
address to 247 if the WHM system is being monitored by a Protonode
with Slave –Slave (SSD) programming. Set to zero (0) if no Protonode
is installed.
16
SSD Temp Format
SSD temp values can be accessed in Degrees or Points
17
1 Valve Status 8
Displays the valve status of all the units.
0= valve closed
1= valve open
2= valve stuck closed
3= valve stuck open
18
1 Comm Errors 8
Display Comm Errors of all the units.
19
20
WHM On Delay
WHM off Delay
Specifies the WHM On and Off time delays associated with the Next
ON VP and Next OFF VP menu options. Therefore, if the Next ON VP
or Next OFF VP is at its preset Valve Position (%) for the specified
Delay period, another heater will be turned ON or OFF. This is done
to prevent cycling units on and off during short changes in load.
21
Over WHM Under
This value is a Factory debugging tool.
22
WHM Min Units
Specifies the Minimum number of units required to be “on” or “active”.
23
WHM Warmup Time
Specifies the time a valve will remain closed when turning on a unit in
order to assure that we do not release cold water into the building.
When turning on a unit, the valve will open when either the Warmup
Timer times out or the FeedForward Temperature reaches Setpoint.
24
WHM On Timeout
Specifies the time the WHM Master waits for a slave unit to turn On.
25
WHM Valve State
Displays the status of the WHM Sequencing Valve.
(1 = ON, 0 = OFF)