5.6.2 Delayed Interlock
Delayed Interlock
1.
Remove the cover from the I/O Box and locate the DELAYED INTL’K IN terminals (see
Figure 2-12).
2.
Start the unit in the Manual mode at a valve position between 25% and 30%.
3.
If there is a jumper across the DELAYED INTL’K IN terminals, remove one side of the
jumper. If the interlock is connected to a proving switch of an external device, disconnect
one of the wires leading to the proving switch.
4.
The unit should shut down and display a
DELAYED INTERLOCK OPEN
fault message.
The
FAULT
LED should be flashing.
5.
Reconnect the wire or jumper removed in step 3 to restore the interlock.
6.
Press the
CLEAR
button to reset the fault.
7.
The unit should start.
5.7 FLAME FAULT TESTS
Flame faults can occur during ignition or while the unit is already running. To simulate each of
these fault conditions, proceed as follows:
Flame Fault Tests
1.
Set the ON/OFF switch to the
OFF
position.
2.
Place the unit in the Manual mode and set the valve position between 25% and 30%.
3.
Close the manual gas shutoff valve located between the Safety Shut-Off Valve (SSOV)
and the Air/Fuel Valve (see Figure 5-3).
4.
Set the ON/OFF switch to the
ON
position to start the unit.
5.
The unit should shut down after reaching the Ignition cycle and display
FLAME LOSS
DURING IGN
.
6.
Open the valve previously closed in step 3 and press the
CLEAR
button.
7.
Restart the unit and allow it to prove flame.
8.
Once flame is proven, close the 1” manual gas shut-off valve located between the SSOV
(Figure 5-3) and the Air/Fuel Valve.
9.
The unit should shut down and execute an IGNITION RETRY cycle by performing the
following:
a) The unit will execute a shutdown purge cycle for a period of 15 seconds and display
WAIT FAULT PURGE
.
b) The unit will execute a 30 second re-ignition delay and display
WAIT RETRY
PAUSE
.
c) The unit will then execute a standard ignition sequence and display
WAIT IGNITION
RETRY
.