Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 8 – WATER HEATER MANAGEMENT
Page
118
of
216
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0078_0M
09/11/2015
Phone: 800-526-0288
GF-128
Table 8-1. WHM Menu
SN Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1. WHM Mode
Off, WHM Slave,
WHM Master
Off
2. WHM Setpoint
40°F (4.4°C)
190°F (87.8°C)
130°F (54.4°C)
3. WHM Nxt On VP
16%
100%
60%
4. WHM Nxt Off VP
16%
100%
30%
5. Lead/Lag Hours
25
225
72
6. WHM Upld Timer
0
9999
0
7. Setpoint Setback
Enable, Disable
Disable
8. Setback Setpoint
40°F (4.4°C)
150°F (65.5°C)
130°F (54.4°C)
9. Setback Start
12:00am
11:59pm
12:00am
10. Setback End
12:00am
11:59pm
12:00am
11. WHM Auto Mstr *
Yes or No
No
12. WHM Auto Timer *
10 sec.
120 sec.
30 sec.
13. WHM min addr
1
8
1
14. WHM max addr
1
8
8
15. SSD address
0
250
0
16. SSD Temp Format
Degrees or Points
Degrees
17. 1 Valve Status 8
0
0
0
18. 1 Comm Errors 8
0
0
0
19. WHM On Delay
30 sec
300 sec
60 sec
20. WHM Off Delay
30 sec
300 sec
60 sec
21. Over WHM Under
0
0
0
22. WHM Min Units
1
8
1
23. WHM Warmup Time
0
300 sec
30 sec
24. WHM On Timeout
15 Sec
300 Sec
30 Sec
25. WHM Valve State
0
1
0
26. Valve Override
Auto, Open or Closed
Auto
27. Valve Feedback
Enable or Disable
Disable
28. Valve Fdbk timer
30 sec
240 sec
60 sec
29. ValveFdbk Status
Close
Open
Fdbk state
30. MB Head Temp En
Enable or Disable
Disable
31. WHM Header Temp
0
0
Header Temp