Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
Page
48
of
216
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0078_0M
09/11/2015
Phone: 800-526-0288
GF-128
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
4 IGN Position
5%
60%
Depends on unit type/size
5 FFWD Temp Disply
Enabled or Disabled
6 Outlet Tmp Dsply
Enabled or Disabled
7 Inlet Tmp Dsply
Enabled or Disabled
8 Valv Pos Out Dsp
Enabled or Disabled
9 Exhaust Tmp Dsp
Enabled or Disabled
10 VP Up Rate
0.5
60.0
Depends on unit type/size
11 VP Down Rate
0.5
60.0
Depends on unit type/size
12 Purge Blwr Offst
-1.0
8.0
Depends on unit type/size
13 4-20mA Purge Pct
60%
100%
70%
14 PWM In Adj
-5.0%
5.0%
0.0%
15 Analog In Adj
-5.0%
5.0%
0.0%
16 Flow In Adj
-5.0%
5.0%
0.0%
17 Supply Gas Pressure In Adj
-5.0%
5.0%
0.0%
18 Gas Plate dp In Adj
-5.0%
5.0%
0.0%
19 mA Out Adj
-1.0 mA
1.0 mA
0.0 mA
20 A/F Sensitivity
1%
5%
2%
21 Power Reset
Automatic or Manual
Automatic
22 Water Temp Reset
Automatic or Manual
Automatic
23 Gas Press Reset
Automatic or Manual
Manual
24 Min Off Time
0 Min
15 Min
0 Min
25 Heatr Tuning Dsp
Enabled or Disabled
Disabled
26 Heatr Bkpt Dsp
Enabled or Disabled
Disabled
27 Stop Level
0%
Start Level
16
28 Start Level
Stop Level
40%
20
29 Skip Range Cntr
10
95
40
30 Skip Range Span
0
3
0
31 Skip Speed
5
20
5
32 O2 Gain
920
1126
1024
33 O2 Offset
-3.0
+3.0
0
34 O2 Sensor
Enabled or Disabled
Depends on unit type/size
35 Cal Temp Sensors
Enabled or Disabled
36 FFWD Temp Offset
-20
+20
0
37 Exhst Tmp Offset
-20
+20
0
38 Outdr Air Offset
-20
+20
0
39 Inlet Air Offset
-20
+20
0