CONTROL PANEL OPERATING PROCEDURES
3-6
3.6. CONFIGURATION
MENU
The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.
NOTE:
The Configuration Menu settings shown in Table
3-4 are Factory-Set in accordance with the
requirements specified for each individual order.
Therefore, under normal operating conditions,
no changes will be required
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
Boiler
Water Heater
Boiler
Unit Size
0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
2.5 MBTU, 3.0 MBTU
1.0 MBTU
Boiler Mode
Constant Setpoint
Remote Setpoint
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
BMS (PWM Input
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Boiler Mode =
Outdoor Reset)
40°F 240°F 70°F
Reset Ratio
(If Boiler Mode =
Outdoor Reset)
0.1 9.9 1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F 100°F 60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
240°F
200°F
Temp Hi Limit
40°F
240°F
215°F
Max Fire Rate
40%
100%
100%
Pump Delay Timer
0 min
30 min
0 min
Aux Start On Dly
0 sec
120 sec
0 sec
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
mA Output
Setpoint, Outlet Temp,
Fire Rate Out, Off
Off
Lo Fire Timer
2 sec
120 sec
2 sec
Setpt Limiting
Enabled or Disabled
Disabled
Setpt Limit Band
0°F
10°F
5°F
Summary of Contents for GF-110 Benchmark Series
Page 6: ......
Page 8: ......
Page 12: ......
Page 32: ......
Page 40: ......
Page 46: ......
Page 52: ......
Page 58: ......
Page 68: ......
Page 76: ......
Page 77: ...APPENDIX C C 1 Temperature Sensor Resistance Chart Balco ...
Page 78: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ...APPENDIX F F 4 ...
Page 89: ...APPENDIX F F 5 ...
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ...APPENDIX F F 9 ...
Page 94: ...APPENDIX F F 10 ...
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ...APPENDIX G G 5 ...
Page 100: ......
Page 101: ...APPENDIX H H 1 ...
Page 102: ...APPENDIX H H 2 ...
Page 104: ...APPENDIX H H 4 ...
Page 105: ...APPENDIX H H 5 ...
Page 106: ...APPENDIX H H 6 ...
Page 108: ......
Page 110: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...
Page 112: ...APPENDIX K K 2 FIGURE 1 DUAL FUEL DIVERTER VALVE FIGURE 2 DUAL FUEL AIR INJECTION VALVE ...
Page 115: ......
Page 116: ......