21
Tab. 15 Cyclic input and output data with Thyro-A 1A...C01
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Load current L1
float
4
[A]
8
Power L1
float
4
[W]
12
Mains voltage L1
integer
2
[V]
14
Switch-on time TS
integer
2
[period]
16
Switch-on angle alpha
integer
2
[0.01 °el]
18
Total setpoint
integer
2
4096=100%
20
Fault (see table 14b)
integer
2
-
22
Status (see table 14b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%
Tab. 16 Cyclic input and output data with Thyro-A 1A...C02
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage phase 1
float
4
[V]
4
Load current phase 1
float
4
[A]
8
Load current phase 2
float
4
[A]
12
Total load current
float
4
[A]
16
Mains voltage L1
integer
2
[V]
18
Switch-on angle alpha phase 1
integer
2
[0.01 °el]
20
Total setpoint
integer
2
4096=100%
22
Fault (see table 14b)
integer
2
-
24
Status (see table 14b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%
Tab. 17 Cyclic input and output data with Thyro-A 1A...C03
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Load current L1
float
4
[A]
8
Power L1
float
4
[W]
12
Mains voltage L1
integer
2
[V]
14
Switch-on time TS
integer
2
[period]
16
Switch-on angle alpha
integer
2
[0.01 °el]
18
Total setpoint
integer
2
4096=100%
20
Fault (see table 14b)
integer
2
-
22
Status (see table 14b)
integer
2
-
Offset
Output data, setpoint values
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%