Tab. 3 Interpretation of the master setpoint with Thyro-S
Tab. 4 Cyclic input and output data with Thyro-S ..H1
Tab. 5 Cyclic input and output data with Thyro-S ..HRL1
Tab. 5b Thyro-S Faults
Setpoint (Master)
Status (return value)
(Total setpoint)
0 to 409
= OFF
0 =
410 to 1091
1/5
819
1092 to 1706
= 1/3
1365 =
1707 to 3071
1/2
2047
3072 to 4096
= ON
4096
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Mains voltage L1
integer
2
[V]
6
Total setpoint
integer
2
4096=100%
8
Fault (see table 5b)
integer
2
-
10
Status (see table 5b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master Setpoint
integer
2
4096=100%
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Load current L1
float
4
[A]
8
Mains voltage L1
integer
2
[V]
10
Total setpoint
integer
2
4096=100%
12
Fault (see table 5b)
integer
2
-
14
Status (see table 5b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%
Description
Bit
LEDs
Relay
Frequency measurement outside of 47 Hz to 63 Hz
Bit 0
Test LED flashing slowly
open
SYNC error, no zero-crossing within the gate
Bit 1
Test LED flashing slowly
open
Temperature monitoring triggered
Bit 2
Load Fault flashing slowly
open
Load fault
Bit 3
Load Fault on
open
Flash values invalid
Bit 4
Test LED and Load Fault LED
flashing simultaneously quickly
open
Mains undervoltage (<AD_P_SPG_MIN)
Bit 5
Load Fault LED and Test LED on
open
Mains overvoltage (>AD_P_SPG_MAX)
Bit 6
None
closed