Tab. 8 Cyclic input and output data with Thyro-A 1A...HRLP1
Tab. 9 Cyclic input and output data with Thyro-A 2A...H1
Tab. 10 Cyclic input and output data with Thyro-A 2A...HRL1
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Load current L1
float
4
[A]
8
Power L1
float
4
[W]
12
Mains voltage L1
integer
2
[V]
14
Switch-on time TS
integer
2
[period]
16
Switch-on angle alpha
integer
2
[0.01 °el]
18
Total setpoint
integer
2
4096=100%
20
Fault (see table 14b)
integer
2
-
22
Status (see table 14b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Load voltage L3
float
4
[V]
8
Mains voltage L1
integer
2
[V]
10
Mains voltage L3
integer
2
[V]
12
Switch-on time TS
integer
2
[period]
14
Total setpoint
integer
2
4096=100%
16
Fault (see table 14b)
integer
2
-
18
Status (see table 14b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%
Offset
Input data, actual values
Data type
Size
Unit
0
Load voltage L1
float
4
[V]
4
Load voltage L3
float
4
[V]
8
Load current L1
float
4
[A]
12
Load current L2
float
4
[A]
16
Load current L3
float
4
[A]
20
Mains voltage L1
integer
2
[V]
22
Mains voltage L3
integer
2
[V]
24
Switch-on time TS
integer
2
[period]
26
Total setpoint
integer
2
4096=100%
28
Fault (see table 14b)
integer
2
-
30
Status (see table 14b)
integer
2
-
Offset
Output data, setpoint
Data type
Size
Unit
0
Master setpoint
integer
2
4096=100%