Name
Set Alarm Limit
Description
Sets the High/Low alarm limit value for the specified input channel of a specified
ADAM-6000 module.
Syntax $aaCjAhU(data)(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadecimal Modbus network address of an
ADAM-6000 module.
(Always 01)
Cj
identifies the desired analog input channel j (j : 0 to 7).
AhU
is the Set Alarm Limit command.
h
indicates alarm type (H = High alarm, L = Low alarm)
(data)
represents the desired alarm limit setting. The format is always in engineering units.
(cr)
represents terminating character, carriage return (0Dh)
Response !aa(cr)
if the command was valid
?aa(cr)
if an invalid operation was entered.
There is no response if the system detects a syntax error or communication error or if the
specified address does not exist.
!
delimiter character indicating a valid command was received.
aa
represents the 2-character hexadecimal Modbus network address of the corresponding
ADAM-6000 module.
(cr)
represents terminating character, carriage return (0Dh)
Example
command:
$080.00(cr)
response:
!01(cr)
The high alarm limit of the channel 1 in the specific ADAM-6000 module at address 01h is
been set +80.
The system confirms the command has been received.
Note:
An analog input module requires a maximum of 2 seconds after it receives a Set
Alarm Limit command to let the settings take effect. During this interval, the module cannot
be addressed to perform any other actions.
$aaCjRhU
Name
Read Alarm Limit
Summary of Contents for ADAM-6000 series
Page 21: ...Figure 3 2 Fix ADAM 6000 module on the bracket...
Page 23: ......
Page 24: ...Figure 3 4 Secure ADAM 6000 Module to a DIN rail...
Page 27: ...Figure 3 6 ADAM 6000 I O Module Terminal Block wiring...
Page 32: ...Figure 4 4 ADAM 6017 Digital Output wiring...
Page 36: ...Figure 4 8 ADAM 6050 Digital Output Wiring...
Page 41: ...Figure 4 13 ADAM 6051 Digital Output and Counter Wiring...
Page 46: ...Figure 4 18 ADAM 6060 Relay Output Wiring...
Page 75: ...Figure 5 29 Firmware Upgrade for ADAM 6000 I O Series Modules...
Page 153: ...Appendix A Design Worksheets...