Name
Set Input Range
Description
Sets the input range for a specified channel of a specified analog input
module.
Syntax $aaAnntt
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadecimal Modbus address
of the ADAM-6000 module you want to configure. (Always 01)
A
represents the set input range command.
nn
(range 00-07) represents the specific channel you want to set the input
range.
tt
(range 0x07-0x0D) represents the 2-character code of the input type.
(Refer to the table below)
(cr)
is the terminating character, carriage return (0Dh).
Signal Type and Range
Against Code
4 ~ 20mA
07
-10V ~ 10V
08
0V ~ 5V
09
-1V ~ 1V
0A
0mV ~ 500mV
0B
-100mV ~ 100mV
0C
0 ~ 20mA
0D
Table 6-4
ADAM-6017 Analog Input Range mapping Table
Response !aa(cr)
if the command is valid.