V6.230 20131017
191
Setting #
Setting
Purpose
Setting Range or Values
Program to
020
SP32 DRPOUT
Probe #3 set point
#2 dropout
temperature
20/nnn
where nnn=-35 to 160
DO NOT SET IF SINGLE
PROBE
021
SP33 PICKUP
Probe #3, set point
#3 pickup
temperature
21/nnn
where nnn=-35 to 160
DO NOT SET IF SINGLE
PROBE
022
SP33 DRPOUT
Probe #3 set point
#3 dropout
temperature
22/nnn
where nnn=-35 to 160
DO NOT SET IF SINGLE
PROBE
023
SP34 PICKUP
Probe #3, set point
#4 pickup
temperature
23/nnn
where nnn=-35 to 160
DO NOT SET IF SINGLE
PROBE
024
SP34 DRPOUT
Probe #3 set point
#4 dropout
temperature
24/nnn
where nnn=-35 to 160
DO NOT SET IF SINGLE
PROBE
025
WSP11 PICKUP
Calculated winding
pickup temperature
25/nnn
where nnn=-35 to 180
SET ONLY IF Aux CT avail.
026
WSP11
DRPOUT
Calculated winding
dropout temperature
26/nnn
where nnn=-35 to 180
SET ONLY IF Aux CT avail.
027
WSP12 PICKUP
Calculated winding
pickup temperature
27/nnn
where nnn=-35 to 180
SET ONLY IF Aux CT avail.
028
WSP12
DRPOUT
Calculated winding
dropout temperature
28/nnn
where nnn=-35 to 180
SET ONLY IF Aux CT avail.
029
WSP13 PICKUP
Calculated winding
pickup temperature
29/nnn
where nnn=-35 to 180
SET ONLY IF Aux CT avail.
030
WSP13
DRPOUT
Calculated winding
dropout temperature
30/nnn
where nnn=-35 to 180
SET ONLY IF Aux CT avail.
Summary of Contents for TTC-1000
Page 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Page 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Page 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Page 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Page 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Page 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Page 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...