V6.230 20131017
168
Setting #
Setting
Purpose
Setting Range or
Values
Factory
Default
Program to
024
OUT8(Action)
w/ALRM
Action: UNCHG,
PCKUP, SUPV,
NOACT
Allows OUT8 default
when a DEVICE or
TPROBE alarm
OUT8UNCHGw/ALRM
does not allow OUT8 to
change state when
alarm
OUT8PCKUPw/ALRM
causes OUT8 to pickup
when alarm
OUT8SUPVw/ALRM
drops out OUT8 when
alarm
OUT8NOACTw/ALRM
prevents output logic
from being processed
OUT8
UNCHG
w/ALRM
025
INVERT OUT1
Master output inversion
OFF, ON
OFF
026
INVERT OUT2
Master output inversion
OFF, ON
OFF
027
INVERT OUT3
Master output inversion
OFF, ON
OFF
028
INVERT OUT4
Master output inversion
OFF, ON
OFF
029
INVERT OUT5
Master output inversion
OFF, ON
OFF
030
INVERT OUT6
Master output inversion
OFF, ON
OFF
031
INVERT OUT7
Master output inversion
OFF, ON
OFF
032
INVERT OUT8
Master output inversion
OFF, ON
OFF
033
CT RATIO1
Sets Primary CT ratio
0 to 9999
0
034
RATED LOAD1
(functional only in
units equipped with
aux CT)
Sets rated load current
0 to 65535 Amps
0
035
WINDINGRISE1
(functional only in
units equipped with
aux CT)
Set hotspot rise above
top oil temperature at
rated load from
manufacturer's heat run
data
0 to 99
C
0
036
CT RATIO2
Sets Primary CT ratio
0 to 9999
0
037
RATED LOAD2
(functional only in
units equipped with
aux CT)
Sets rated load current
0 to 65535 Amps
0
038
WINDINGRISE2
(functional only in
units equipped with
aux CT)
Set hotspot rise above
top oil temperature at
rated load from
manufacturer's heat run
data
0 to 99
C
0
Summary of Contents for TTC-1000
Page 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Page 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Page 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Page 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Page 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Page 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Page 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...