Temperature Set Points
The TTC-1000 has four independent temperature set points per temperature
probe and each probe has four calculated winding set points associated with it if
used with a CT and the options for winding temperature calculation are set. Each
set point has its own pick up and drop out temperatures. The pick up and drop
out temperature can be set at different temperatures and allows the controller to
operate as either an under or over temperature controller. The following two
equations describe how the controller reacts depending on the setting of the pick
up and drop out temperature for liquid temperature probes:
If SPpn Pick UP > = SPpn Drop Out then operate as over temperature
If SPpn Pick UP < SPpn Drop Out then operate as under temperature
Where: p = Probe # (1, 2 or 3) & n = Set point # (1, 2, 3, 4)
The equations for winding temperature pickup and drop temperatures are:
If WSPn Pick UP > = WSPn Drop Out then operate as over temperature
If WSPn Pick UP < WSPn Drop Out then operate as under temperature
Where: n = Set point # (1, 2, 3, 4)
The over temperature set point is ideal for handling the pickup of fans or pumps
as well as generating over temperature alarms and trip signals. The under
temperature feature is useful to block the operation of pumps at low
temperatures.
Figure 4.1 and 4.2 show
when the SP picks up and
drops out for when the
controller is configured to
operate in the over and
under temperature modes
respectively.
Figure 4.1: Over
Temperature Operation
SPpn Pick Up
Temperature
SPpn Drop Out
Temperature
Temperature
Time
SPpn
Summary of Contents for TTC-1000
Page 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Page 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Page 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Page 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Page 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Page 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Page 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...