13
–
✱
80
OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
Notes:
1.
For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
2.
For Powerline Carrier devices (plcd), field
✱
27 must be programmed with a House Code.
3
. Tampers of expansion units cannot be used to operate devices.
Activation Type and Detail
Event (for zone list/activated by)
Output
Function
Number
(1-48)
Activated by
0=delete
1=zn list
2=zn type
3=zn no.
Zone List
(ZL)
1-8 = list
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
01-64
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 = partition 2
3 = common
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
By Zone No.
0 = restore
1 = alrm/flt/trbl
Action
0 = off
1 = close 2 secs
2 = stay closed
3 = pulse
4 = toggle
5 = duration 1
††
6 = duration 2
††
Output
Number
1-18= dev
Device
Type
R = relay
T = trigger
X = X10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used
05 = Trouble Day/Alarm Night 10 = Interior w/Delay
24 = Silent Burglary
01 = Entry/Exit#1
06 = 24 Hr Silent
12 = Monitor Zone
25 = 24-Hr Non-Alarm
02 = Entry/Exit#2
07 = 24 Hr Audible
14 = Carbon Monoxide
§§
77 = Keyswitch
03 = Perimeter
08 = 24 Hr Aux
16 = Fire w/Verification
81 = AAV Monitor Zone
04 = Interior Follower
09 = Fire
23 = No Alarm Response
90-93 = Configurable
§§ when used with an output function,
the carbon monoxide zone type
activates only upon CO alarms. Does
not activate for trouble conditions.
Choices for System Operation are:
20 = Arming–Stay
38 = Chime
58 = Duress
21 = Arming–Away
39 = Any Fire Alarm
60 = AAV Trigger
22 = Disarming (Code + OFF)
40 = Bypassing
61 = AVS/GSMV session begin §
31 = End of Exit Time
41 = **AC Power Failure
62 = AVS/GSMV session end §
32 = Start of Entry Time
42 = **System Battery Low
66 = Function key†
33 = Any Burglary Alarm
43 = Communication Failure
67 = Bell Failure
36 = **At Bell Timeout***
52 = Kissoff
68 = Telco Line Fault
54 = Fire Zone Reset
78 = Keyswitch red LED†††
79 = Keyswitch green LED†††
Note:
In normal operation mode:
Code + # + 7 + NN Key Entry
starts
Device
Code + # + 8 + NN Key Entry
stops
Device
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
†† Duration is set in program field *177.
††† Device action not used for these choices.
§ automatically set when appropriate AVS Quick
Command performed.