16
–
Type 20
Arm-Stay
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.
Type 21
Arm-Away
•
Arms the system in Away mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.
Type 22
Disarm
•
Disarms the system when the zone is activated.
•
User code for button must be assigned.
Type 23*
No Alarm Response
•
Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
Type 24
Silent Burglary
•
Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
•
Provides an instant alarm, with NO audible indication at any touchpad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, or Instant, modes.
•
A report is sent to the central station.
Type 25*
24-Hour Non-Alarm
•
For use with sensors designed to provide a trouble display (but no trouble sounding) when an oil tank is
low, or other similar application for critical condition monitoring where a non-alarm response is required.
•
When this zone type is faulted and remains faulted for the programmed time duration (field *53), a special
event message is sent to the central monitoring station. The same holds true for restoration.
Type 77
Keyswitch
•
Assign to zone wired to a keyswitch.
Type 81
AAV Monitor Zone
•
Assign to zone connected to AAV module.
•
Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting stops, except for fire alarms,
which immediately terminate the voice session and cause a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell timeout has not expired)
and reports that were stopped are sent.
Types 90-93
Installer Defined
•
These zone types can be programmed for various custom responses. See data fields *182-*185.
•
Types 92 and 93 can only be programmed via the downloader.
UL: Zone types 90-93 may not be used as fire or burglary zones in fire or UL burglar alarm installations.
*
The system can still be armed when these zone types are in a faulted condition.
Table of Device Addresses
This Device
Uses
Address
Reports as
†
Enabled By…
RF Receiver
00
100
*56 zone programming: input device type entry
AUI 1 (touchscreen)
01
n/a
automatic if AUI enable field *189 enabled for AUI 1
AUI 2 (touchscreen)
02
n/a
automatic if AUI enable field *189 enabled for AUI 2
AUI 3 (touchscreen)
05
n/a
automatic if AUI enable field *189 enabled for AUI 3
AUI 4 (touchscreen)
06
n/a
automatic if AUI enable field *189 enabled for AUI 4
Communication Device (LRR)
03
103
automatic if communication device enabled in *29 menu mode
4286 Voice Module
04
104
automatic if phone module access code field *28 enabled
Zone Expanders (4219/4229):
module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 (for zones 33 - 40)
module 5 (for zones 41 - 48)
07
08
09
10
11
107
108
109
110
111
*56 zone programming: input device type, entry 2, then:
automatic if zone no. 9-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay
assigned
automatic if zone no. 25-32 entered as AW type or relay
assigned
automatic if zone no. 33-40 entered as AW type or relay
assigned
automatic if zone no. 41-48 entered as AW type or relay
assigned
Relay Modules (4204):
module 1
module 2
module 3
module 4
12
13
14
15
112
113
114
115
*79 output device programming: device address prompt:
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
Touchpads:
touchpad 1
touchpad 2
touchpad 3
touchpad 4
touchpad 5
touchpad 6
touchpad 7
touchpad 8
16
17
18
19
20
21
22
23
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
data field programming as listed below:
always enabled for partition 1, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
HSPIM Module
25
n/a
automatic
5800TM Module
28
n/a
automatic
†
Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device reporting
(default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification touchpad display options.